Resumen
The application of very sensitive ground-fault protection in underground coal mines was demonstrated in the early 1980s for low- and medium-voltage utilization circuits (less than 1 kV), but its commercial application did not occur until the advent of high-voltage utilization circuits on longwalls in the late 1980s. With these high-voltage systems (greater than 1000 V), the Mine Safety and Health Administration initially required a maximum ground-fault resistor current limit of 3.75 A for 4160-V systems and 6.5 A for 2400-V systems in 101-c Petitions for Modification. However, more recent Petitions for Modification have been required to limit maximum ground-fault resistor currents to 1.0 A, or even 0.5 A. Standard practice in other industries generally requires high-resistance grounding to be designed so that the capacitive charging current of the system is less than or equal to the resistor current under a ground-fault condition. The intent of this practice is to prevent the system from developing some of the undesirable characteristics of an ungrounded system, such as overvoltages from inductive-capacitive resonance effects and intermittent ground faults. Shielded cables, which have significantly more capacitance than their unshielded counterparts, are required for high-voltage applications in the mining industry. Thus, with the long cable runs of a high-voltage longwall system, capacitive charging currents may exceed grounding-resistor currents under ground-fault conditions. An analysis of a typical 4160-V longwall power system that utilizes very-high-resistance grounding (grounding-resistor-current limit of 0.5 A) is performed to determine whether or not potential problems exist.
| Idioma original | English |
|---|---|
| Páginas (desde-hasta) | 104-111 |
| Número de páginas | 8 |
| Publicación | IEEE Transactions on Industry Applications |
| Volumen | 37 |
| N.º | 1 |
| DOI | |
| Estado | Published - ene 2001 |
ASJC Scopus subject areas
- Control and Systems Engineering
- Industrial and Manufacturing Engineering
- Electrical and Electronic Engineering
Huella
Profundice en los temas de investigación de 'Analysis of very-high-resistance grounding in high-voltage longwall power systems'. En conjunto forman una huella única.Citar esto
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver