Ir directamente a la navegación principal Ir directamente a la búsqueda Ir directamente al contenido principal

Detrimental effects of capacitance on high-resistance-grounded mine distribution systems

Producción científica: Article › revisión exhaustiva

10 Citas (Scopus)

Resumen

Modern underground coal mines can be very large, having a total connected load in excess of 15 000 hp. These mines generally have many miles of high-power conveyor belts and 15 or more miles of high-voltage power cables at distribution voltages of 12.47, 13.2, 13.8, or 14.4 kV. The shielded cables used in mine power distribution systems have a significant level of capacitance, on the order of 110 pF/ft. This level of capacitance, in an extensive power distribution system at today's voltage levels, can cause significant charging currents during a ground fault. This paper addresses the potential detrimental effects of capacitance charging currents during line-to-ground faults in mine power distribution systems. A representative mine power system is modeled, and simulations with faults at various locations are conducted to evaluate the effects of this capacitance on the level of fault current and relay selectivity. This paper also includes results of capacitance measurements made on mine power feeder cables used to validate the simulation model.

Idioma originalEnglish
Páginas (desde-hasta)1333-1339
Número de páginas7
PublicaciónIEEE Transactions on Industry Applications
Volumen42
N.º5
DOI
EstadoPublished - sept 2006

Nota bibliográfica

Funding Information:
Paper PID-06-03, presented at the 2005 Industry Applications Society Annual Meeting, Hong Kong, October 2–6, and approved for publication in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS by the Mining Industry Committee of the IEEE Industry Applications Society. Manuscript submitted for review October 15, 2005 and released for publication June 3, 2006. This work was supported by the National Institute for Occupational Safety and Health (NIOSH), Pittsburgh Research Laboratory, under Contract 200-2002-000589, Reduction of Mining Electrical Hazards Through Improved Engineering Controls, with Dr. J. L. Kohler as the Technical Project Officer.

Financiación

Paper PID-06-03, presented at the 2005 Industry Applications Society Annual Meeting, Hong Kong, October 2–6, and approved for publication in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS by the Mining Industry Committee of the IEEE Industry Applications Society. Manuscript submitted for review October 15, 2005 and released for publication June 3, 2006. This work was supported by the National Institute for Occupational Safety and Health (NIOSH), Pittsburgh Research Laboratory, under Contract 200-2002-000589, Reduction of Mining Electrical Hazards Through Improved Engineering Controls, with Dr. J. L. Kohler as the Technical Project Officer.

FinanciadoresNúmero del financiador
Pittsburgh Research Laboratory200-2002-000589
National Institute for Occupational Safety and Health

    ASJC Scopus subject areas

    • Control and Systems Engineering
    • Industrial and Manufacturing Engineering
    • Electrical and Electronic Engineering

    Huella

    Profundice en los temas de investigación de 'Detrimental effects of capacitance on high-resistance-grounded mine distribution systems'. En conjunto forman una huella única.

    Citar esto