Power transmission line parameter estimation and optimal meter placement

Producción científica: Conference contributionrevisión exhaustiva

30 Citas (Scopus)

Resumen

This paper puts forth a framework for estimating the transmission line parameters (including series resistance and reactance and shunt susceptance), line temperature and sag employing synchronized phasors obtained by Phasor Measurement Units (PMU) in real time. The estimated temperature and sag can be utilized for dynamic thermal rating for increased power transfer. The proposed algorithms harness the non-linear optimal estimation theory, and are capable of detecting and identifying bad measurement data, minimizing impacts of measurement errors and thus significantly improving the estimation accuracy. In addition, this paper proposes an optimal scheme for placing PMUs in the system such that a minimum number of PMUs need to be installed in order to determine the parameters, temperature and sag of all the concerned transmission lines in a power network.

Idioma originalEnglish
Título de la publicación alojadaIEEE SoutheastCon 2010
Subtítulo de la publicación alojadaEnergizing Our Future
Páginas250-254
Número de páginas5
DOI
EstadoPublished - 2010
EventoIEEE SoutheastCon 2010 Conference: Energizing Our Future - Charlotte-Concord, NC, United States
Duración: mar 18 2010mar 21 2010

Serie de la publicación

NombreConference Proceedings - IEEE SOUTHEASTCON
ISSN (versión impresa)1091-0050
ISSN (versión digital)1558-058X

Conference

ConferenceIEEE SoutheastCon 2010 Conference: Energizing Our Future
País/TerritorioUnited States
CiudadCharlotte-Concord, NC
Período3/18/103/21/10

ASJC Scopus subject areas

  • Signal Processing
  • Computer Networks and Communications
  • Software
  • Electrical and Electronic Engineering
  • Control and Systems Engineering

Huella

Profundice en los temas de investigación de 'Power transmission line parameter estimation and optimal meter placement'. En conjunto forman una huella única.

Citar esto